Skip to calculator

⚡ Voltage Drop Calculator

Find the voltage drop, drop percentage, and voltage reaching the load — from wire gauge, run length, and current. DC, single-phase, and three-phase, with a 3% NEC check. Free, no sign-up.

✓ Volts & percentage drop ✓ 3% NEC pass / fail check ✓ Free — no sign-up needed
📌 Quick Answer

A voltage drop calculator finds how much voltage is lost in a wire run before it reaches the load. Every conductor has resistance, and current flowing through that resistance loses voltage along the way. The calculator returns the drop in volts, the drop as a percentage, and the voltage left at the load. The core formulas are:

DC / 1-phase: Drop = 2 × I × R × Length  |  3-phase: Drop = √3 × I × R × Length  |  Drop % = Drop ÷ Source Voltage

How to calculate voltage drop in 3 steps:

  1. Pick a wire gauge and material, or enter a known resistance directly.
  2. Enter the voltage, load current, and one-way distance, and choose DC, single-phase, or three-phase.
  3. Click Calculate to see the drop in volts, the percentage, and the voltage at the load.

For example, 12 AWG copper carrying 15 A over a 50-foot single-phase run drops about 2.9 volts — 2.4% of a 120-volt supply, leaving 117 volts at the load. That passes the 3% recommendation.

Voltage Drop Calculator

Enter wire gauge, distance, and current — see the voltage drop and what reaches the load.

📊 Wire gauge or custom resistance — DC, single & three-phase
V
A
ft
Distance is the one-way run to the load — the calculator accounts for the return conductor
Voltage Drop
volts
of supply
Voltage
Current
Distance
Voltage at Load
Wire Resistance (Ω)
Power Lost (W)
3% Limit Check
Voltage Drop Percentage
%
V lost ·
Where the Voltage Goes: Supply · Drop · At the Load
Supply
Drop
At Load
Enter your circuit and calculate to see where the voltage goes.
Voltage drop, percentage, and load voltage are exact arithmetic from standard conductor resistance values. Real circuits vary with temperature and connection quality — always follow local electrical codes for final wire sizing.
⚡ Wire Sizing Made Simple

Know How Much Voltage Reaches the Load –
Before You Pull the Wire

Every foot of wire has resistance, and resistance steals voltage. On a long run, what arrives at the load can be noticeably less than what left the panel. This free calculator turns wire gauge, distance, and current into an exact voltage drop — and checks it against the 3% guideline.

⚡ Try the Calculator Now
3%
branch circuit guideline
5%
feeder plus branch
1.6×
aluminum vs copper
13
wire sizes
📖 Introduction

The Voltage That Leaves the Panel Isn't the Voltage That Arrives

Plug something in and you assume it gets the full voltage. On a short run, near enough. On a long one, not really. Wire has resistance, and resistance quietly skims voltage off the top the whole way to the load — so what arrives can be meaningfully less than what left the breaker.

It comes down to one chain of cause and effect. Every conductor has resistance. Push current through resistance and you lose voltage — that is Ohm's law. The longer the run, the smaller the wire, or the higher the current, the bigger the loss. Too much of it and motors run hot, lights dim, and electronics misbehave.

This Voltage Drop Calculator turns that into hard numbers. Pick a wire gauge, or enter a resistance directly; add the voltage, current, distance, and phase; and it returns the drop in volts, the drop as a percentage, the voltage left at the load, and whether the circuit clears the 3% recommendation.

Pro Tip: Voltage drop scales directly with distance. Double the run and you double the drop. So the moment a circuit gets long, the question stops being "what wire carries this current?" and becomes "what wire keeps the drop in check over this distance?" — and the answer is often a size or two larger.
⚙️ How It Works

How the Voltage Drop Calculator Works

Pick a mode, fill in the circuit, click once. Here is what each field does.

1

Choose a Mode

Wire Gauge mode uses standard AWG resistance values — just pick a size and material. Custom Resistance mode lets you type in an ohms-per-distance figure straight from a spec sheet.

2

Set the Wire & Phase

In Wire Gauge mode, choose copper or aluminum and the AWG size. Then pick the system: DC, AC single-phase, or AC three-phase — each uses a different multiplier.

🟠 Copper has lower resistance than aluminum.
3

Enter the Voltage

The system voltage — 12, 120, 240, 480, or whatever your circuit runs at. The drop is compared against this to give the percentage.

4

Enter the Load Current

The current the load draws, in amps. Voltage drop is directly proportional to current — a heavier load on the same wire means a bigger drop.

⚡ More amps, more drop.
5

Enter the One-Way Distance

The distance from the source to the load — one direction only. The calculator doubles it for the return conductor on DC and single-phase circuits.

6

Calculate — Read the Drop

Instantly see the voltage drop in volts, the percentage, the voltage at the load, the power lost as heat, and a pass-fail check against your drop limit.

✅ Drop % = Voltage drop ÷ Source voltage
Reality Check: The 3% pass-fail flag is a recommendation, not a law. The National Electrical Code suggests 3% for a branch circuit, but it does not strictly forbid more. The flag tells you whether your circuit lands inside good practice — a fail means it is worth a larger wire, not that it is unsafe.
🔬 The Formula

The Voltage Drop Formula, Explained

Voltage drop is Ohm's law applied to a wire run. The whole thing rests on V = I × R.

The base idea. Voltage drop equals current times resistance. The current is what your load draws; the resistance is the resistance of the wire it travels through. The only real work is figuring out how much wire the current actually passes through.

Why distance is doubled. On a DC or single-phase circuit, current leaves the source through one conductor and returns through another. So it travels through twice the one-way distance. That is why the formula is 2 × current × resistance-per-foot × one-way distance — the 2 accounts for the round trip.

The three-phase difference. A balanced three-phase circuit shares current across three conductors, and the math works out to a factor of √3 — about 1.732 — instead of 2. Same idea, different multiplier, because the current path is arranged differently.

A worked example. Take 12 AWG copper, which has about 1.93 ohms per 1,000 feet, carrying 15 amps over a 50-foot single-phase run. The drop is 2 × 15 × 1.93 × (50 ÷ 1000) = 2.9 volts. On a 120-volt supply that is 2.9 ÷ 120 = 2.4% — and 117 volts reaches the load.

Parallel conductor sets change one term. Running two identical sets side by side halves the effective resistance, which halves the drop. The calculator divides the wire's resistance by the number of sets before doing the rest.

The percentage is the figure that matters: Three volts of drop sounds alarming on a 12-volt system and trivial on a 480-volt one. Expressing the drop as a percentage of the source voltage is what makes it comparable — and it is the percentage, not the raw volts, that codes and guidelines are written around.
📊 Wire Data

Wire Gauge & Resistance Tables

The resistance of common wire sizes, and the drop limits worth knowing. These are the numbers the calculator works from.

Wire SizeCopper (Ω/1000 ft)Aluminum (Ω/1000 ft)
14 AWG3.075.06
12 AWG1.933.18
10 AWG1.212.00
8 AWG0.7641.26
6 AWG0.4910.808
4 AWG0.3080.508
2 AWG0.1940.319
1/0 AWG0.1220.201
2/0 AWG0.09670.159
4/0 AWG0.06080.100

The core formula in plain words: voltage drop equals the phase factor — 2 for DC and single-phase, 1.732 for three-phase — times the current, the resistance per foot, and the one-way distance. Divide by source voltage for the percentage.

Voltage Drop Limits

CircuitRecommended LimitWhy
Branch circuit3%The NEC recommendation for the final run to a load
Feeder plus branch5%The combined total the NEC suggests as a ceiling
Sensitive electronics2%Tighter, where stable voltage matters most
Long DC / low-voltage runsvaries12V systems are very sensitive to drop

How Far 12 AWG Copper Carries 15 A Before 3% Drop

System VoltageApprox. Max One-Way RunNote
120 V~62 ftA typical household branch circuit
240 V~124 ftHigher voltage tolerates a longer run
12 V DC~6 ftLow voltage drops out very fast

The same wire and current behave completely differently by voltage. This is why low-voltage DC runs need surprisingly heavy wire over even short distances.

🔍 Key Factors

Factors That Affect Voltage Drop

Five things move the drop. Change any one and the number changes with it.

📏
Run Length
The single biggest lever. Voltage drop is directly proportional to distance — a run twice as long has twice the drop. Long circuits almost always need a larger wire than the current alone would suggest.
🔌
Wire Gauge
A thicker wire has lower resistance per foot, so it loses less voltage. Going up one or two gauge sizes is the standard cure for a circuit that fails the drop check.
Load Current
Drop rises in step with current. The same wire over the same distance loses more voltage to a heavy load than a light one — heavy loads and long runs are a demanding combination.
🔋
System Voltage
Drop as a percentage depends on the source voltage. The same volts lost is a small fraction of 480 V but a large fraction of 12 V — which is why low-voltage systems are so drop-sensitive.
🟠
Conductor Material
Copper conducts better than aluminum. For the same gauge, aluminum has roughly 1.6 times the resistance, so an aluminum run drops more voltage than a copper one of the same size.
🔀
Phase Type
DC and single-phase use a factor of 2 for the round-trip conductor; three-phase uses √3. The same wire and load produce a different drop depending on the system.
⚖️
Parallel Sets
Running conductors in parallel splits the current and lowers the effective resistance. Two identical sets halve the drop — a common approach on large feeders.
🌡️
Temperature
Conductor resistance rises with temperature. A wire running warm under load has slightly more resistance than the cool-table value, so real drop can edge above the calculated figure.
⚡ Conductors & Phases

Copper vs Aluminum & Phase Types

Two choices shape the result before you touch a number: the conductor metal, and the type of electrical system.

🟠
Copper
Lower R
resistance
1.93
Ω/1000ft (12 AWG)
Less drop
Per gauge
Aluminum
~1.6×
copper's R
3.18
Ω/1000ft (12 AWG)
Lighter, cheaper
Big feeders
Single-Phase
×2
distance factor
120 / 240 V
typical
Homes
Most circuits
🔌
Three-Phase
×1.732
distance factor
208 / 480 V
typical
Commercial
Industry
ChoiceEffect on DropTypical Use
CopperLower resistance, less drop per gaugeBranch circuits, most residential wiring
AluminumHigher resistance; needs a larger size to match copperService entrances and large feeders
DCFactor of 2 for the return conductorSolar, automotive, low-voltage systems
AC single-phaseFactor of 2, same as DCHomes and light commercial
AC three-phaseFactor of √3 (1.732)Commercial and industrial power
Switching mode changes only the resistance source: Wire Gauge mode reads resistance from a standard AWG table. Custom Resistance mode takes a value you supply. The voltage drop math afterward — current, distance, phase factor — is identical either way.
🛠️ Wire Sizing

How to Size Wire for a Run: A Phase-by-Phase Roadmap

Picking a wire size is two questions answered in order — can it carry the current, and can it keep the drop in check. Here is the path.

Phase 1 · Start With the Load
Know the current and the distance

Find the load's current draw in amps and measure the one-way run from the source to the load. These two figures, with the system voltage, define the whole problem.

Gather: current, one-way distance, voltage
Phase 2 · Size for Ampacity First
Pick a wire that can carry the current

Every wire size has an ampacity — the current it can safely carry. Start with the smallest gauge rated for your load current. This is the safety floor, set by code, before drop is even considered.

Rule: never go below the code ampacity
Phase 3 · Check the Voltage Drop
Run that gauge through the calculator

Enter the ampacity-sized wire here. If the drop comes in under 3%, the gauge works on both counts. If it fails, the run is too long for that size — move to the next phase.

Target: 3% or less on a branch circuit
Phase 4 · Upsize Until It Passes
Step up a gauge and recheck

If the drop is too high, go up one wire size and calculate again. Repeat until the drop clears the limit. The final choice is whichever gauge satisfies both ampacity and voltage drop.

Pro move: let the stricter of the two rules win
💸 The Cost

The Real Cost of Voltage Drop

Voltage drop is not just a number on a form. It costs money in two ways — wasted energy now, and shortened equipment life later.

Every volt dropped in the wire is energy turned into heat instead of useful work. On a long, heavily loaded run, that lost power adds up on the electricity bill, year after year, doing nothing but warming the cable. Upsizing the wire trades a one-time material cost for a permanent reduction in that loss.

The second cost is harder to see. Equipment fed low voltage works harder to do its job. Motors draw extra current and run hotter, which shortens their life. Lighting dims and electronics can behave unpredictably. The price of excessive drop shows up later as premature failures and service calls.

🔥
Wasted Energy
Lost as heat in the wire
CauseDrop × current
Shows upOn the bill
FixLarger wire
A steady, ongoing loss
⚙️
Equipment Strain
Motors and electronics
CauseLow voltage
Shows upEarly failures
FixStay under 3%
A hidden long-term cost
🔌
Upsizing the Wire
The one-time cure
CauseBigger gauge
Shows upUp-front cost
PaybackYears of savings
Pay once, save for decades
Plan the wire size before the run is pulled: Voltage drop is cheap to fix on paper and expensive to fix in a wall. Choosing the right gauge before installation costs only the price difference in copper. Discovering the problem after the cable is buried means tearing it out and starting over.
💡 Real Examples

Example Voltage Drop Calculations

Three circuits, three outcomes — each worked through with verified math so you can check your own.

EXAMPLE 1An Undersized Long Branch Circuit
🔌 Wire: 14 AWG copper 🔋 System: 120 V single-phase 📏 Distance: 100 ft ⚡ Current: 12 A
Voltage Drop
7.4 V · 6.1%
2 × 12 × 3.07 × (100 ÷ 1000) = 7.4 V
🔴 Fails — Upsize the Wire At 6.1%, this run is well past the 3% recommendation, leaving only 113 volts at the load. The wire is too thin for 100 feet. Moving from 14 AWG to 10 AWG would roughly cut the drop to about 2.4%, bringing it back into range.
EXAMPLE 2An Aluminum Feeder Run
🔌 Wire: 2 AWG aluminum 🔋 System: 240 V single-phase 📏 Distance: 200 ft ⚡ Current: 50 A
Voltage Drop
6.4 V · 2.7%
2 × 50 × 0.319 × (200 ÷ 1000) = 6.4 V
🟢 Passes — Just Aluminum has more resistance than copper, but the 240-volt supply does the heavy lifting here. The 6.4-volt drop is only 2.7% of 240, sliding under the 3% line. The same wire on a 120-volt system would have failed at 5.3%.
EXAMPLE 3A Three-Phase Industrial Run
🔌 Wire: 4 AWG copper 🔋 System: 480 V three-phase 📏 Distance: 300 ft ⚡ Current: 40 A
Voltage Drop
6.4 V · 1.3%
1.732 × 40 × 0.308 × (300 ÷ 1000) = 6.4 V
🟢 Comfortably Within Limits Three-phase uses the 1.732 factor instead of 2, and 480 volts is a large base to measure against. Even over 300 feet, the drop is just 1.3% — a reminder that higher-voltage three-phase systems tolerate long runs far better than 120-volt circuits.
📋 Best Practice

Keeping Voltage Drop Under Control

Good wire sizing is mostly a few habits applied before the cable is ever pulled. These are the ones that matter.

The first habit is checking drop on every run that is even moderately long. Short circuits rarely have a problem, so they get a pass — but a run of fifty feet or more, especially at 120 volts, deserves a quick calculation. Catching a marginal circuit on paper is free; catching it after the wall is closed is not.

The second is treating ampacity and voltage drop as two separate hurdles, both of which the wire must clear. A gauge can be perfectly safe for the current and still drop too much voltage over distance. When the two rules disagree, the larger wire wins — that is the size that satisfies both.

Six Habits for Controlling Voltage Drop

📏
Check every long run. Any circuit over about fifty feet deserves a voltage drop calculation before the wire size is locked in.
🔌
Size for ampacity and drop both. The wire has to carry the current safely and keep the drop in range — let the stricter of the two set the gauge.
⬆️
Upsize early on long runs. When a circuit is long, plan on a larger gauge from the start rather than discovering the shortfall after installation.
🟠
Account for the conductor metal. Aluminum needs a size or two larger than copper to land at the same voltage drop — never swap them gauge-for-gauge.
🔋
Watch low-voltage runs closely. A 12-volt DC circuit hits its drop limit in a fraction of the distance a 120-volt one would — they need heavier wire than people expect.
📋
Follow the local code. Voltage drop guidance and wire sizing rules are set by the NEC and local amendments — confirm the requirements that apply to your job.
⚠️ Limitations

When This Calculator Is the Wrong Tool

The arithmetic here is exact, but a real electrical installation has factors a quick calculation does not capture. Here is where the output needs an expert's eye.

1. It uses resistance only, not full impedance. On AC circuits, conductors also have reactance, and in steel conduit that reactance is significant. This calculator works from DC resistance, which is accurate for most planning but slightly optimistic for large AC conductors in metallic conduit.

2. It does not size for ampacity. Voltage drop is only half of wire sizing. The wire must also be rated to carry the current safely without overheating. Always confirm the gauge against code ampacity tables — this tool does not.

3. Resistance values are at a reference temperature. Conductor resistance rises as the wire heats under load. The table values assume a standard temperature, so a hot circuit will drop slightly more voltage than calculated.

4. It assumes a balanced, steady load. The math is for a constant current draw. Motors drawing heavy startup current, or unbalanced three-phase loads, behave differently and need a more detailed analysis.

Where to go instead: For code-critical work, a licensed electrician and the full NEC conductor tables are the authority — including Chapter 9 Table 9 for AC impedance in conduit. This calculator is a fast, accurate planning tool for estimating drop and comparing wire sizes, not a substitute for a code-compliant design.

📚 Glossary

Electrical Terms You'll See On This Page

Quick reference for the electrical terms used throughout this calculator.

Voltage Drop
The voltage lost in a conductor as current flows through its resistance, between the source and the load.
Resistance
A conductor's opposition to current flow, measured in ohms. It rises with length and falls with wire size.
AWG
American Wire Gauge — the standard sizing system for wire. A smaller AWG number means a thicker wire.
Ampacity
The maximum current a conductor can carry continuously without overheating, set by code.
Ohm's Law
The relationship V = I × R — voltage equals current times resistance — the basis of the drop formula.
One-Way Distance
The length of the run measured in a single direction, from the source to the load.
Phase Factor
The multiplier in the drop formula — 2 for DC and single-phase, 1.732 for three-phase.
Conductor
The metal wire that carries current — usually copper or aluminum.
NEC
The National Electrical Code, the US standard for electrical installation, including voltage drop guidance.
Parallel Sets
Two or more identical conductor runs wired side by side to share current and lower effective resistance.
Branch Circuit
The final wiring run between the last overcurrent device and the load it serves.
Feeder
A circuit between the service equipment and a branch-circuit panel further down the line.
Load Current
The current, in amps, that the connected equipment draws from the circuit.
Voltage at Load
The voltage actually reaching the equipment — the source voltage minus the voltage drop.
❓ FAQ

Frequently Asked Questions

The most common questions about calculating and controlling voltage drop.

How do I calculate voltage drop?

Voltage drop equals the current multiplied by the wire's total resistance. For a DC or single-phase circuit, the formula is 2 × current × resistance per foot × one-way distance, because the current travels out to the load and back. For three-phase, the factor is the square root of 3 instead of 2.

What is an acceptable voltage drop?

The National Electrical Code recommends keeping voltage drop at or below 3 percent on a branch circuit, and no more than 5 percent total across the feeder and branch combined. These are recommendations, not hard rules — but staying within them protects equipment performance and efficiency.

Why does voltage drop matter?

Voltage that is lost in the wire never reaches the device. Excessive drop makes motors run hot, lights dim, and electronics behave unreliably, and the lost energy is wasted as heat in the cable. Sizing the wire to limit drop keeps equipment running as designed.

How does wire length affect voltage drop?

Voltage drop is directly proportional to the length of the run. Double the distance and you double the drop. This is why long circuits often need a larger wire gauge than a short run carrying the same current — the extra copper offsets the added resistance.

Does a bigger wire reduce voltage drop?

Yes. A larger wire has a lower resistance per foot, so it loses less voltage for the same current and distance. Going up one or two gauge sizes is the standard fix for a circuit that fails the voltage drop check on a long run.

What is the difference between copper and aluminum wire for voltage drop?

Aluminum has a higher resistance than copper for the same gauge, so an aluminum conductor produces more voltage drop than a copper one of the same size. To match copper's performance, aluminum wire generally needs to be one or two sizes larger.

Why is the distance doubled in the voltage drop formula?

In a DC or single-phase circuit, current flows from the source to the load through one conductor and returns through another. The total wire the current passes through is twice the one-way distance, so the formula multiplies the one-way length by two.

How do I calculate voltage drop for three-phase?

For a balanced three-phase circuit, voltage drop equals the square root of 3 (about 1.732) multiplied by the current, the resistance per foot, and the one-way distance. The factor is 1.732 rather than 2 because of how current is shared across the three conductors.

What is voltage drop percentage?

Voltage drop percentage is the voltage lost in the wire divided by the source voltage, expressed as a percent. A 120-volt circuit that drops 3.6 volts has a 3 percent voltage drop. The percentage is the figure usually compared against code recommendations.

Does adding parallel conductor sets reduce voltage drop?

Yes. Running two identical sets of conductors in parallel halves the effective resistance, which halves the voltage drop. Parallel sets are common on large feeders where a single conductor would otherwise need to be impractically large.

What causes high voltage drop?

The main causes are a long wire run, a wire gauge that is too small for the current, a high load current, and using aluminum where copper would do better. High voltage drop is almost always solved by shortening the run or increasing the wire size.

How accurate is this voltage drop calculator?

The calculation is exact arithmetic from the figures you enter, using standard conductor resistance values. Real circuits also have temperature effects and, on AC, a small reactance component. For most planning it is highly accurate — for code-critical work, confirm against NEC conductor tables.

⚡ Free · Instant · No Sign-Up

Check Your Voltage Drop
in 30 Seconds

Enter wire gauge, distance, current, and voltage — get the voltage drop in volts and percent, the voltage at the load, and a check against the 3% guideline. All free.

Calculate Drop — Free Takes 30 seconds · No account needed · AWG & custom resistance
Drop in volts & percent
Copper & aluminum
AC & DC, all phases
Checks the 3% guideline
Free forever
Disclaimer: The voltage drop, percentage, and load voltage in this calculator are exact arithmetic from the figures you enter, using standard conductor resistance values. It uses conductor resistance, which is very close to the true value for typical building circuits; large conductors and steel conduit add AC effects that a full NEC impedance method accounts for. This tool provides estimates for educational and planning purposes only. It does not size conductors for ampacity and is not a substitute for a licensed electrician. Wire sizing, circuit protection, and installation are governed by electrical codes — always confirm the requirements that apply to your project and work with a qualified professional.